3 – Interior, Doors, Windows
3.2.1 – Ceilings & Walls
Ceilings & Walls 1
ASBESTOS CEILING
THROUGHOUT PROPERTY

The property had ceiling materials that may contain asbestos. Ceiling tiles or popcorn textures were manufactured or installed using asbestos as late as the early 90s.

In the past, asbestos fibers were added during production to strengthen and increase durability. Materials that contain asbestos, when intact and in good condition, are generally considered non-friable and not hazardous. Heat, water, weathering, or aging can weaken asbestos materials to the point where it is considered friable. Friable material includes any material containing more than 1 percent asbestos that can be crumbled, pulverized, or reduced to powder with hand pressure. This includes previously non-friable material which has been damaged to the extent that it may be crumbled, pulverized, or reduced to powder by hand pressure and can also be made friable during its removal. Friable materials can release asbestos fibers into the air. Once in the air, asbestos fibers present a health hazard to people who inhale those fibers.

3.2.2 – Ceilings & Walls
Ceilings & Walls 2
Ceilings & Walls 3
Ceilings & Walls 4
MISSING – BASEBOARD TRIM
THROUGHOUT PROPERTY

Baseboard trim was missing in areas of the interior walls at the time of inspection. A qualified contractor should evaluate and repair or replace as needed.

3.3.1 – Floors
Floors 1
CARPET STAINS

The carpet was stained in areas. A qualified contractor should evaluate and repair or replace as necessary.

3.3.2 – Floors
Floors 2
THE CARPET REVEALED A SEEM
BACK LEFT BEDROOM LIVING ROOM

The carpet revealed a seam.  A qualified contractor should evaluate and repair or replace as necessary.

3.3.3 – Floors
Floors 3
Floors 4CARPET DAMAGED
DINING ROOM

The carpet was damaged in areas. A qualified contractor should evaluate and repair or replace as necessary.

3.3.4 – Floors

Floors 5

Floors 6

Floors 7

CARPET LOOSE
THROUGHOUT PROPERTY

The carpet was loose or baggy and may need to be restretched.  A qualified contractor should evaluate and repair or replace as necessary.

3.3.5 – Floors
FLOOR SQUEAKS
THROUGHOUT PROPERTY

The floor squeaks when stepped on.  A qualified contractor should evaluate and repair or replace as necessary.

3.5.1 – Windows
Windows 1
BROKEN SEALS
BACK LEFT BEDROOM

The window appeared to have a broken seal that has been compromised.  Condensation and/or cloudiness between the two panes of glass was observed.  This will have a negative impact on energy efficiency.  Also, because there is moisture between the panes with no ventilation, mold can eventually develop.  A qualified contractor should evaluate and repair or replace as necessary.

3.5.2 – Windows
Windows 2
DIFFICULT TO OPEN/CLOSE
LIVING ROOM

A window had a sash that was difficult to slide or operate to get opened/closed.  A qualified contractor should evaluate and repair or replace as necessary.

3.5.3 – Windows
Windows 3
DAMAGED SEALANT/GLAZING

Interior window(s) had deteriorated or damaged glazing. Significant deterioration is enough to loosen the glass pane from the frame. A qualified contractor should evaluate and repair or replace as necessary.

3.5.4 – Windows
Windows 4
WORN OR NEARING THE END OF LIFE EXPECTANCY
THROUGHOUT PROPERTY

Windows installed in the home appeared to be worn or aged. This apparent condition can mean the windows are deteriorated or difficult to operate, and can also mean they are not consistent with current efficiency standards. They were possibly original and were either at or near their serviceable lifespan. Recommend further evaluation by a qualified contractor and budgeting for potential future replacement.

3.5.5 – Windows

Windows 5

SCREENS DAMAGED/MISSING
THROUGHOUT PROPERTY

Some windows had damaged or missing screens.  A qualified contractor should evaluate and repair or replace as necessary.

3.7.1 – Electrical Fixtures & Switches
FAN WOBBLES
DINING ROOM

The ceiling fan wobbles when operated and may need to be balanced.  A qualified contractor should evaluate and repair or replace as necessary.

3.8.1 – Stairways & Railings
Stairways & Railings 1
NO RETURN AT ENDS
BASEMENT STAIRWAY

At the interior stairs, the handrail had a railing end that did not return to the wall or post.  A fall could occur if something (purse, backpack, etc.) caught the end of the railing when descending. A fall or injury could occur if not corrected. A qualified contractor should evaluate and repair or replace as necessary.

3.8.2 – Stairways & Railings
Stairways & Railings 2
SPINDLE SPACING OVER 4″

At the interior stairs, the handrail had spacing between components that were too far apart. Spacing of more than 4 ” could allow a child or pet to fall through. A fall or injury could occur if not corrected.  A qualified contractor should evaluate and repair or replace as necessary.

3.9.1 – Smoke & CO Detectors
Smoke & CO Detectors 1
SMOKE DETECTOR OLD
THROUGHOUT PROPERTY

Some of the smoke detectors appeared to be old and beyond their expected life. A qualified person should repair or replace as needed. The existing smoke detectors were tested if present, but they are only noted as to presence and operation as of the date of inspection. Smoke detectors may work today but not work when you need them to work. This is why it is important for you to test them on a regular basis, monthly at least. Smoke detectors are recommended by the U.S. Product Safety Commission to be installed inside each bedroom and adjoining hallway and on each living level of the property and basement level.

 4 – Exterior – Condo/Townhome
4.1.1 – Walkways & Driveways
Walkways & Driveways 1
HEAVING AND/OR SETTLING

The walkway(s) showed signs of heaving and/or settling in areas. Heaving is often caused by soil that has expanded in volume due to increased moisture content, or by wet soil which has expanded as it became frozen.

  • This causes cracks in the concrete.
  • This creates trip hazards that could result in injury.

A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

4.1.2 – Walkways & Driveways
Walkways & Driveways 2
MODERATE CRACKING – WALKWAY

There were signs of moderate cracking at the walkway. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

4.2.1 – Exterior Doors
Exterior Doors 1
DAMAGE – SCREEN DOOR

The screen door was damaged or deteriorated at the time of inspection.

A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

4.4.1 – Electrical Outlets
Electrical Outlets 1
NO EXTERIOR GFCI PROTECTION
BACK

No Ground Fault Circuit Interrupter (GFCI) protection was provided for the exterior electrical outlets. Although GFCI protection of exterior circuits may not have been required at the time in which this property was built, modern building and safety standards now require them. This is a reflection of the current understanding of the potential hazards. The inspector recommends updating the existing exterior electrical circuits to include GFCI protection. A qualified contractor should evaluate and implement according to current standards.

4.4.2 – Electrical Outlets
Electrical Outlets 2
MISSING WEATHERPROOF COVERING
BACK

The exterior electrical outlet was missing a weatherproof covering. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

4.5.1 – Exterior Vents
Exterior Vents 1
Exterior Vents 2
WASP NEST

There are wasp nests present in the vent hood covers at the time of the inspection a qualified pest control professional should investigate and remove them.

 5 – Kitchen
5.4.1 – Floors
Floors 1
FLOOR DAMAGED
KITCHEN

There appeared to be some damage to the interior flooring in areas. Recommend a qualified contractor to evaluate and repair or replace as needed.

5.5.1 – Cabinets & Counters
Cabinets & Counters 1
DAMAGED – CABINET FLOOR
KITCHEN

The cabinet floor was damaged. This may be from excessive leaking pipes, condensation, or even leaking cleaners stored in cabinets over the years.

A qualified contractor should evaluate and repair or replace as necessary.

5.5.2 – Cabinets & Counters
Cabinets & Counters 2
OVERLAPPING

Doors handles, and/or drawers overlap and open into each other in the kitchen. This either restricts both items to be opened simultaneously, or requires one to be opened for another to be usable. Recommend a qualified contractor to evaluate and repair or replace as necessary.

5.5.3 – Cabinets & Counters
Cabinets & Counters 3
Cabinets & Counters 4
WORN FINISH
KITCHEN

Counters or cabinetry had a finish that was worn or peeling. Recommend a qualified contractor to evaluate and repair or replace as needed.

5.6.1 – Electrical Outlets
Electrical Outlets 1
Electrical Outlets 2
Electrical Outlets 3
NO GFCI PROTECTION
KITCHEN

No ground fault circuit interrupter (GFCI) protection was provided for kitchen electrical outlets. Although GFCI protection of kitchen circuits may not have been required at the time in which this property was built, as general knowledge of safe building practices has improved with the passage of time building standards have changed to reflect current understanding. The inspector recommends updating the existing kitchen electrical circuits to provide GFCI protection. This can be achieved by:

1. Replacing the current standard outlets with GFCI outlets.

2.  Replacing the first circuit outlet located closest to the main electrical service panel with the GFCI outlet

3.  Replacing the breaker currently protecting the electrical circuit that contains these outlets with the GFCI breaker.

A qualified contractor should evaluate and repair or replace as necessary.

5.7.1 – Windows
Windows 1
SCREENS DAMAGED/MISSING
KITCHEN

Some windows had damaged or missing screens.  A qualified contractor should evaluate and repair or replace as necessary.

 6 – Laundry
6.4.1 – Exhaust Fan
FAN NEEDED

There was no ventilation (exhaust fan or openable window) In the laundry area. Normally an exhaust fan or an openable window is needed for proper ventilation.  A qualified contractor should evaluate and repair or replace as necessary.

6.5.1 – Ceilings & Walls
Ceilings & Walls 1
TAPE AND BED
LAUNDRY AREA

The drywall in some areas revealed the tape and nail bed. A qualified contractor should evaluate and repair or replace as necessary.

6.9.1 – Electrical Outlets
Electrical Outlets 1
GFCI PROTECTION IS NOT PRESENT
LAUNDRY AREA

An outlet did not provide Ground Fault Circuit Interrupter (GFCI) protection. Although GFCI protection of circuits may not have been required at the time in which this home was built, safe building practices have improved with the passage of time and building standards have changed to reflect current understanding. The inspector recommends updating the existing electrical circuits to include GFCI protection. A qualified contractor should evaluate and repair or replace as necessary.

 9 – Bathroom
9.4.1 – Ceilings & Walls
Ceilings & Walls 1
MOISTURE STAINING-CEILINGS
PRIMARY BATHROOM

The ceiling showed wet staining indicating moisture intrusion did or does still exist.  A qualified contractor should evaluate and repair or replace as necessary.

9.4.2 – Ceilings & Walls
Ceilings & Walls 2
MOISTURE STAINING-WALLS
PRIMARY BATHROOM

The wall showed wet staining indicating moisture intrusion did or does still exist.  A qualified contractor should evaluate and repair or replace as necessary.

9.4.3 – Ceilings & Walls
Ceilings & Walls 3
TAPE AND BED
PRIMARY BATHROOM

The drywall in some areas revealed the tape and nail bed. A qualified contractor should evaluate and repair or replace as necessary.

9.5.1 – Floors
Floors 1
CARPET BY SHOWER, TOILET AREAS

Carpeting was used as a floor covering material in the tub, shower, and/or toilet areas. The carpet is bound to get wet from steam/vapor from the shower, splashing, and water dripping off a body. Carpet tends to act as a sponge and soak up the moisture, which gives mildew and molds an opportunity to grow and spread. Recommend a qualified contractor to evaluate and replace the floor covering materials as needed.

9.7.1 – Electrical Outlets
Electrical Outlets 1
NO GFCI PROTECTION
PRIMARY BATHROOM

No ground fault circuit interrupter (GFCI) protection was provided for the bathroom electrical outlets. Although GFCI protection of bathroom circuits may not have been required at the time in which this property was built, as general knowledge of safe building practices has improved with the passage of time building standards have changed to reflect current understanding. The inspector recommends updating the existing bathroom electrical circuits to provide GFCI protection. This can be achieved by:

1. Replacing the current standard outlets with GFCI outlets.

2.  Replacing the first circuit outlet located closest to the main electrical service panel with the GFCI outlet

3.  Replacing the breaker currently protecting the electrical circuit that contains these outlets with the GFCI breaker.

A qualified contractor should evaluate and repair or replace as necessary.

9.8.1 – Electrical Fixtures & Switches
Electrical Fixtures & Switches 1
NOT WORKING – BULB
PRIMARY BATHROOM

One or more bulbs were not working in the bathroom at the time of inspection.

Recommend a qualified contractor to evaluate and repair or replace as needed.

9.14.1 – Tub, Shower Area
Tub, Shower Area 1
POSSIBLE MOLD

Evidence of a possible mold-like substance was observed bath or shower area.  We did not inspect, test, or determine if this growth is or is not a health hazard. The underlying cause is moisture. It is recommended to consult a mold inspector or mold remediation specialist to determine if further action is needed. Further analysis by a mold remediation specialist is recommended. Axium recommends our premier partner – Mold Removal Express. They can be contacted at 720-464-1555 or online at www.axiuminspections.com/mold-removal-express.

9.14.2 – Tub, Shower Area
Tub, Shower Area 2
STAINED, DIRTY

The shower pan or tub is dirty and possibly stained at the time of the inspection. Recommend further evaluation from a qualified professional for cleaning, repairs, or replacement.

 10 – Bathroom 2
10.5.1 – Floors
Floors 1
CARPET BY SHOWER, TOILET AREAS
2ND FLOOR HALL BATHROOM

Carpeting was used as a floor covering material in the tub, shower, and/or toilet areas. The carpet is bound to get wet from steam/vapor from the shower, splashing, and water dripping off a body. Carpet tends to act as a sponge and soak up the moisture, which gives mildew and molds an opportunity to grow and spread. Recommend a qualified contractor to evaluate and replace the floor covering materials as needed.

10.5.2 – Floors
Floors 2
Floors 3
CARPET LOOSE
2ND FLOOR HALL BATHROOM

The carpet was loose or baggy and may need to be restretched.  A qualified contractor should evaluate and repair or replace as necessary.

10.7.1 – Electrical Outlets
Electrical Outlets 1
NO GFCI PROTECTION

No ground fault circuit interrupter (GFCI) protection was provided for the bathroom electrical outlets. Although GFCI protection of bathroom circuits may not have been required at the time in which this property was built, as general knowledge of safe building practices has improved with the passage of time building standards have changed to reflect current understanding. The inspector recommends updating the existing bathroom electrical circuits to provide GFCI protection. This can be achieved by:

1. Replacing the current standard outlets with GFCI outlets.

2.  Replacing the first circuit outlet located closest to the main electrical service panel with the GFCI outlet

3.  Replacing the breaker currently protecting the electrical circuit that contains these outlets with the GFCI breaker.

A qualified contractor should evaluate and repair or replace as necessary.

10.9.1 – Cabinets & Counters
Cabinets & Counters 1
DAMAGED – CABINET FLOOR
2ND FLOOR HALL BATHROOM

The cabinet floor was damaged. This may be from excessive leaking pipes, condensation, or even leaking cleaners stored in cabinets over the years.

A qualified contractor should evaluate and repair or replace as necessary.

10.10.1 – Drain Waste and Vent System
Drain Waste and Vent System 1
CLOGGED/SLOW – TUB/SHOWER DRAIN
2ND FLOOR HALL BATHROOM

The tub/shower drain line was clogged or drains slowly. A qualified contractor should evaluate and repair or replace as necessary.

10.12.1 – Plumbing Fixtures
Plumbing Fixtures 1
CHIPPED – SINK
2ND FLOOR HALL BATHROOM

The sink finish was chipped or damaged.  A qualified contractor should evaluate and repair or replace as necessary.

10.12.2 – Plumbing Fixtures
Plumbing Fixtures 2
LOOSE-TUB FAUCET
2ND FLOOR HALL BATHROOM

The tub faucet/spout was loose.  A qualified contractor should evaluate and repair or replace as necessary.

10.12.3 – Plumbing Fixtures
Plumbing Fixtures 3
SEAL TUB SPOUT
2ND FLOOR HALL BATHROOM

The tub spout should be sealed at the wall to prevent moisture intrusion into the wall component. A qualified contractor should evaluate and then repair or replace as advised.

10.12.4 – Plumbing Fixtures
Plumbing Fixtures 4
RUST AND DETERIORATION
2ND FLOOR HALL BATHROOM

The overflow drain is surrounded by Russian and appears to have deteriorated. A qualified plumber should investigate and repair or replace as necessary.

10.14.1 – Tub, Shower Area
Tub, Shower Area 1
BULGE – SHOWER WALL
2ND FLOOR HALL BATHROOM

The shower wall was bowed or bulged in some areas.  A qualified contractor should evaluate and repair or replace as necessary.

10.14.2 – Tub, Shower Area
Tub, Shower Area 2
POSSIBLE MOLD

Evidence of a possible mold-like substance was observed bath or shower area.  We did not inspect, test or determine if this growth is or is not a health hazard. The underlying cause is moisture. It is recommended to consult a mold inspector or mold remediation specialist to determine if further action is needed. Further analysis by a mold remediation specialist is recommended. Axium recommends our premier partner – Mold Removal Express. They can be contacted at 720-464-1555 or online at www.axiuminspections.com/mold-removal-express.

10.14.3 – Tub, Shower Area
Tub, Shower Area 3
GROUT REPAIRED WITH CAULK

Caulking in the shower/tub area was repaired using caulk at the time of inspection. This may not be a long-term solution. Recommend a qualified contractor to evaluate and repair or replace as necessary.

 11 – Bathroom 3
11.7.1 – Electrical Outlets
Electrical Outlets 1
NO GFCI PROTECTION
1ST FLOOR BATHROOM

No ground fault circuit interrupter (GFCI) protection was provided for the bathroom electrical outlets. Although GFCI protection of bathroom circuits may not have been required at the time in which this property was built, as general knowledge of safe building practices has improved with the passage of time building standards have changed to reflect current understanding. The inspector recommends updating the existing bathroom electrical circuits to provide GFCI protection. This can be achieved by:

1. Replacing the current standard outlets with GFCI outlets.

2.  Replacing the first circuit outlet located closest to the main electrical service panel with the GFCI outlet

3.  Replacing the breaker currently protecting the electrical circuit that contains these outlets with the GFCI breaker.

A qualified contractor should evaluate and repair or replace as necessary.

 12 – Plumbing
12.5.1 – Drain, Waste, & Vent Systems
Drain, Waste, & Vent Systems 1
Drain, Waste, & Vent Systems 2
LEAKING – DRAIN LINE

The drain pipe was actively leaking at the time of inspection.  A qualified contractor should evaluate and repair or replace as necessary.

12.5.2 – Drain, Waste, & Vent Systems
Drain, Waste, & Vent Systems 3
Drain, Waste, & Vent Systems 4
CORROSION

Some of the main drain line components were corroded at the time of inspection. Recommend a qualified contractor to evaluate and repair or replace as needed.

 13 – Electrical
13.6.1 – Electrical Wiring
Electrical Wiring 1
Electrical Wiring 2
Electrical Wiring 3
SOLID ALUMINUM BRANCH-CIRCUIT WIRING

Solid conductor aluminum branch-circuit wiring was present. This is an electrical hazard. A qualified contractor should evaluate the electrical system and repair or replace it as necessary.

The aluminum wire appears to be installed on branch electrical circuits in the subject premises. These single-strand, branch circuit aluminum wires were used widely in houses during the mid-1960s and 1970s. According to the U.S. Consumer Product Safety Commission, problems due to expansion can cause overheating at connections between the wire and devices (switches and outlets) or at splices, which has resulted in fires. For further information on aluminum, wiring contact the U.S. Consumer Product Safety Commission via the Internet at http://www.cpsc.gov.

For more details, visit InterNACHI’s Free Inspection Library.

 14 – Water Heating Equipment
14.1.1 – General Information
OLDER THAN 10 YEARS

The water heater was at or beyond its warranty and/or expected life expectancy.

The water heater age was determined by the photo included in this report. According to the U.S. Department of energy, these major appliances are intended to run for between 8 and 12 years. Be advised that every water heater will age differently relative to the following life span factors: water quality, mineral buildup, frequency of flushing, the volume of water utilized, size of the tank, brand, and quality of water heater. Although it was operating at the time of the inspection, the inspector can not determine the remaining life of the water heater.

14.12.1 – Operation & Response to Controls
Operation & Response to Controls 1
FLAMES

Flames were not entirely burning a blue color. Orange and yellow flames may be an indicator that the fuel-air mixture is not right and gas may not be burning as efficiently as possible. Recommend a qualified contractor evaluate to adjust, repair, or replace fuel-burning components as necessary.

 15 – Heating
15.10.1 – Blower
Blower 1
BLOWER WHEEL DIRTY

The blower motor and/or wheel appeared to be dirty at the time of inspection. Blower fan motors and fan wheels are subjected to constant dirt, dust, and lint and can become overly dirty when not cleaned on a regular basis and even faster if the air filters are not changed regularly.

A qualified contractor should evaluate, clean, and service as necessary, and certify the unit is in good working order.

15.12.1 – Heating System Ignition & Operation
Heating System Ignition & Operation 1
Heating System Ignition & Operation 2
THE HEATING SYSTEM IS NOT OPERATIONAL

The heating system did not respond to the demanding heat or did not function properly at the time of the inspection. No shut-off switches were activated aside from the safety shut-off switch that is designed to kill power when the blower cabinet cover is removed. A qualified contractor should evaluate and repair or replace as necessary.

Although the thermostat was set to heat and to the warmest setting available, the air conditioning did not kick off and the furnace did not kick on.  I believe the issue is with the thermostat and not with the furnace itself.

 16 – Cooling
16.1.1 – Cooling System Information
BEYOND TYPICAL LIFE EXPECTANCY

Due to the year of manufacture, the cooling system is assumed to be near the end of its expected service life. Regular maintenance and monitoring of its condition is recommended. Budgeting for repairs and future replacement is recommended. A qualified contractor should evaluate to clean, service/repair/replace as necessary, and certify the unit if possible.  InterNACHI’s Standard Estimated Life Expectancy Chart for Homes

16.1.2 – Cooling System Information
SERVICING RECOMMENDED

Based on the age of the cooling system it is recommended that it be cleaned and serviced and certified (if possible) by an HVAC professional.

16.2.1 – AC Refrigerant Lines
AC Refrigerant Lines 1
AC Refrigerant Lines 2
DAMAGED INSULATION

The air-conditioner refrigerant suction line (large, insulated) has damaged or missing insulation in areas. A qualified contractor should evaluate and repair/replace as necessary.

16.3.1 – AC Compressor
AC Compressor 1
UNIT IS NOT LEVEL

The exterior compressor unit was not level. Over time, this may result in noisy fan operation, damage to the fan bearings, and a shortened fan lifespan, or it may result in movement of the compressor housing which can cause leaks in refrigerant lines resulting in expensive service. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

 17 – Structural Basement
17.5.1 – Moisture Intrusion
Moisture Intrusion 1
EFFLORESCENCE

Efflorescence (white powdery substance) on the wall indicates moisture is in contact with the concrete or masonry. This does not necessarily indicate that intrusion will occur. I recommend checking the gutters and the downspout drain lines for proper operation. Also, a waterproofing paint could be applied to the interior side of the wall if necessary. Efflorescence is found on many properties without water intrusion occurring inside the property. But, it should alert you to the possibility that future steps may be needed. A qualified contractor should evaluate and repair as necessary.

17.7.1 – Insulation
NO INSULATION

There is no insulation on the basement exterior walls or floor system. Heat loss can occur more on this property than on one that is properly insulated. A qualified contractor should evaluate and install as necessary.

17.8.1 – Vapor Barriers
VAPOR BARRIER NOT INSTALLED

A vapor barrier was not installed in the basement at the time of the inspection. A qualified contractor should evaluate and install as necessary.

17.10.1 – Plumbing in Basement
BASEMENT PLUMBING LEAK

There were signs of an active leak in the plumbing system of the basement. A qualified contractor should evaluate and repair or replace as necessary.