2 – Roof
2.8.1 – Masonry Chimney
Masonry Chimney 1
DAMAGE – BRICKS

One or more bricks on the chimney stack were cracked, broken, or deteriorated at the time of inspection. A qualified contractor should evaluate, then repair or replace as advised prior to the inspection objection deadline.

2.8.2 – Masonry Chimney
Masonry Chimney 2
MISSING – RAIN CAP/SPARK ARRESTOR

The chimney rain cap/spark arrestor was missing. A qualified contractor should evaluate, then repair or replace as advised prior to the inspection objection deadline.

A rain cap covers the top opening of the chimney flue liner and is usually combined with a spark arrestor.

A spark arrestor is used to prevent floating embers from a solid fuel fire setting light to a flammable roofing surface or falling onto other combustible materials on the ground. A spark arrestor typically consists of a double layer of metal mesh, which catches the ember and allows the flue gas to escape. Spark arrestors also help prevent animals from entering the chimney.

2.8.3 – Masonry Chimney
Masonry Chimney 3
TUCKPOINTING NEEDED
The chimney had deteriorated mortar joints at the time of inspection and may require repairs such as “tuck-pointing” or “re-pointing”. This is a common maintenance task for masonry. A qualified contractor should evaluate, then repair or replace as advised prior to the inspection objection deadline.
2.8.4 – Masonry Chimney
Masonry Chimney 4
LOOSE BRICKS
Loose bricks on a masonry chimney.
2.9.1 – Roof Drainage Systems
Roof Drainage Systems 1
MISSING GUTTERS

The gutters were missing in areas.  A qualified contractor should evaluate and repair or replace as necessary.

 3 – Attic, Insulation, and Ventilation
3.1.1 – Attic Access
Attic Access 1
OPENING TOO SMALL

The attic hatch was not the proper size to access the attic itself. The rough framed opening must measure a minimum of 22 by 30 inches to allow a full-grown adult to safely enter and exit. Should there be an appliance in the attic, the dimensions may be required to increase to allow the appliance to be removed.

The 2012 International Residential Code requires an attic access opening for attics with an area greater than 30 square feet and a vertical height in excess of 30 inches.

 4 – Exterior
4.4.1 – Wall-Covering, Flashing & Trim
Wall-Covering, Flashing & Trim 1
CRACKING AND MOVEMENT

Cracking from apparent wall movement was present in the siding at the time of inspection.

Monitoring the walls of the house is needed. Most materials including masonry can deform elastically over long periods of time to accommodate small amounts of movement, large movements normally cause cracking.

Cracking can result from a variety of problems:

  • Differential settlement of the foundation
  • Drying shrinkage
  • Expansion and contraction due to ambient thermal and moisture variations
  • Improper support over openings
  • The effects of freeze-thaw cycles
  • The corrosion of iron and steel wall reinforcement
  • Differential movement between building materials; expansion of salts
  • The bulging or leaning of walls.

Recommend a qualified contractor should evaluate and repair or replace as necessary and according to current standards.

4.4.2 – Wall-Covering, Flashing & Trim
Wall-Covering, Flashing & Trim 2
DETERIORATION

The exterior wall covering is beginning to deteriorate or has deteriorated.

Recommend a qualified contractor should evaluate and repair or replace as needed.

4.4.3 – Wall-Covering, Flashing & Trim
Wall-Covering, Flashing & Trim 3
SEAL GAPS AT INTERSECTIONS
MULTIPLE AREAS

Gaps at intersections of the siding, trim, and door and window openings, as well as any other holes in the siding, should be sealed with an appropriate sealant to prevent water penetration into the wall system. A qualified contractor should evaluate and repair or replace as necessary.

4.4.4 – Wall-Covering, Flashing & Trim
Wall-Covering, Flashing & Trim 4
TUCKPOINTING NEEDED

A common maintenance task for brick masonry is the repair of mortar joints. The longevity of mortar joints will vary with the exposure conditions and the mortar materials used, but a life span of more than 25 years is typical. The longevity of brick, however, may well exceed 100 years. Consequently, occasional repair of the mortar joints is expected over the life of the brick masonry. It is our observation that the most common reason for repointing brick masonry is to improve water penetration resistance. Repointing deteriorated mortar joints is one of the most effective and permanent ways of decreasing water entry into brickwork. This is because the most common means of water entry into a brick masonry wall is through de-bonded, cracked, or deteriorated mortar joints. A qualified contractor should evaluate and repair all areas as necessary.

4.5.1 – Eaves, Soffits & Fascia
Eaves, Soffits & Fascia 1
DETERIORATED, ROTTED

Components of the eaves, facia, and/or soffit were deteriorated or rotted. Adjacent portions may also have signs of water damage and be warped, swollen, or have peeling paint and will eventually begin to rot if left untreated or the cause has not been corrected.

A qualified contractor should evaluate and repair or replace as necessary.

4.6.1 – Exterior Doors
Exterior Doors 1
PEELING PAINT

An entry door had areas of peeling paint.  A qualified contractor should evaluate and repair or replace as necessary.

4.8.1 – Electrical Outlets
Electrical Outlets 1
NO EXTERIOR GFCI PROTECTION

No Ground Fault Circuit Interrupter (GFCI) protection was provided for the exterior electrical outlets. Although GFCI protection of exterior circuits may not have been required at the time in which this property was built, modern building and safety standards now require them. This is a reflection of the current understanding of the potential hazards. The inspector recommends updating the existing exterior electrical circuits to include GFCI protection. A qualified contractor should evaluate and implement according to current standards.

4.10.1 – Window Wells
Electrical Outlets 1
Electrical Outlets 2WINDOW NO WELL

The property had basement windows at grade level without window wells installed. This could allow water intrusion into the property at this point. A qualified contractor should evaluate and repair/replace as necessary.

4.11.1 – Walkways
Walkways 1
CRACK AT STEP(S)

Cracking or separation was present at the concrete step(s) in areas. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

4.11.2 – Walkways
Walkways 2
Walkways 3
Walkways 4
HEAVING AND/OR SETTLING

The walkway(s) showed signs of heaving and/or settling in areas. Heaving is often caused by soil that has expanded in volume due to increased moisture content, or by wet soil which has expanded as it became frozen. Settlement is when the soil below a concrete slab is loose or it can no longer support the weight causing it to sink or crack.

  • This causes cracks in the concrete.
  • This creates trip hazards that could result in injury.

A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

4.11.3 – Walkways
Walkways 5
NOT SEALED PROPERLY

A walkway was not properly sealed against a foundation wall and may allow excess moisture to enter. Recommend a qualified contractor and repair or replace as needed.

4.12.1 – Vegetation, Grading & Drainage
Vegetation, Grading & Drainage 1
Vegetation, Grading & Drainage 2
DEFECT – RETAINING WALL
The retaining wall was not installed properly or was not stable. Recommend a qualified contractor should evaluate and repair or replace as necessary and according to current standards.
4.14.1 – Exterior Faucets (Hose Bibs)
Exterior Faucets (Hose Bibs) 1
DAMAGED/LOOSE KNOB

The outside water faucet has a damaged, missing, or loose knob. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

4.14.2 – Exterior Faucets (Hose Bibs)
Exterior Faucets (Hose Bibs) 2
LOOSE IN WALL
One or more exterior faucet was loose in the wall. The faucet should be securely fastened to the wall using appropriate screws depending on the material at the location of the faucet. Recommend a qualified contractor to evaluate and repair or replace as needed.
4.20.1 – Railings & Handrails
Railings & Handrails 1
HORIZONTAL RAILINGS
The guard/handrail had horizontal railings. This creates a climbing risk and a fall or injury could occur if not corrected. A fall or injury could occur if not corrected. A qualified contractor should evaluate and repair or replace as necessary.
4.20.2 – Railings & Handrails
Railings & Handrails 2
Railings & Handrails 3
MISSING – HANDRAIL
A stairway of more than 3 steps or drop of over 30″ was missing a handrail.

 

4.20.3 – Railings & Handrails
Railings & Handrails 4

Railings & Handrails 5

SPINDLE SPACING OVER 4″

Improper spacing was noted between balusters, spindles, and rails. This is a safety hazard, especially for small children.

Guards may not allow the passage of a sphere 4 inches in diameter.

Correction and further evaluation are recommended.

4.21.1 – Roof Drainage – Downspouts & Extensions
Roof Drainage - Downspouts & Extensions 1
MISSING – EXTENSIONS

The downspout (s) are missing the proper 6 ft. extensions. This condition may cause problems by introducing excessive amounts of moisture to the soil beneath the foundation. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

 5 – Interior, Doors, Windows
5.2.1 – Ceilings & Walls
Ceilings & Walls 1
Ceilings & Walls 2
MODERATE CRACKS-CEILINGS
Moderate cracking was visible on the interior ceilings.  A qualified contractor should evaluate and repair or replace as necessary.
5.3.1 – Floors

Floors 1SLOPED

The floor has a dip or is sloped in areas.

Recommend a qualified contractor to evaluate and repair or replace as needed.

5.3.2 – Floors
Floors 2
WEAR AND TEAR

The floors showed signs of minor damage and wear, particularly in high-traffic areas.  A qualified contractor should evaluate and repair or replace as necessary.

5.4.1 – Doors
Floors 1
SWINGS OVERSTEP

The door swings over the top step of the stairwell when opened.  This can lead to a fall and is considered a safety hazard.  A qualified contractor should evaluate and repair or replace as necessary.

5.5.1 – Windows
Windows 1
DAMAGED – SPRING RAIL

The spring rail assembly is damaged or not secured to the window sash. This may cause the sash to fail to stay open if not corrected. Recommend a qualified contractor to evaluate and repair or replace as necessary.

5.5.2 – Windows
Windows 2
NO EGRESS

At the time of the inspection, the property did not have emergency escape and rescue openings that met generally-accepted current standards. Egress opening requirements:

For safety reasons, all sleeping rooms and basements greater than 200 square feet and new properties should meet the generally-accepted current standards for emergency escape and rescue openings, which include the following requirements:

1. Sill height shall not exceed 44 inches above the floor.

2. Minimum net clear opening shall be 5.7 square feet; exception – grade level windows

may have a minimum clear opening of 5 square feet.

3. Minimum net clear opening height shall be 24 inches.

4. Minimum net clear opening width shall be 20 inches.

5.6.1 – Electrical Outlets
Electrical Outlets 1
Electrical Outlets 2
NOT GROUNDED – OUTLET
One or more electrical outlets were not grounded. A qualified contractor should evaluate and repair or replace as necessary.
5.7.1 – Electrical Fixtures & Switches
Electrical Fixtures & Switches 1
HANGS BY WIRE
The light fixture was hanging by the electrical wiring.  A qualified contractor should evaluate and repair or replace as necessary.
5.8.1 – Stairways & Railings
Stairways & Railings 1
HEADROOM
At the interior stairs, the steps did not have sufficient headroom.  The minimum stair tread to ceiling measurement is 6’8″ (6’6″ for a spiral staircase) A fall or injury could occur if not corrected.  A qualified contractor should evaluate and repair or replace as necessary.
5.8.2 – Stairways & Railings
Stairways & Railings 2
MISSING – HANDRAIL

At the interior stairs, the handrail was missing.  A fall or injury could occur if not corrected. A qualified contractor should evaluate and repair or replace as necessary.

5.8.3 – Stairways & Railings
Stairways & Railings 3
NOT INSTALLED PROPERLY
At the interior stairs, the steps were not installed in a satisfactory and safe manner.  A fall or injury could occur if not corrected.  A qualified contractor should evaluate and repair or replace as necessary.
5.9.1 – Smoke & CO Detectors
Smoke & CO Detectors 1
SMOKE DETECTOR MISSING

The smoke detector was missing. A qualified person should replace them as needed. The existing smoke detectors were tested if present, but they are only noted as to presence and operation as of the date of inspection. Smoke detectors may work today but not work when you need them to work. This is why it is important for you to test them on a regular basis, monthly at least. Smoke detectors are recommended by the U.S. Product Safety Commission to be installed inside each bedroom and adjoining hallway and on each living level of the property and basement level.

 6 – Kitchen
6.5.1 – Cabinets & Counters
Cabinets & Counters 1
DAMAGED – CABINET FLOOR
The cabinet floor was damaged. This may be from excessive leaking pipes, condensation, or even leaking cleaners stored in cabinets over the years.

A qualified contractor should evaluate and repair or replace as necessary.

6.9.1 – Faucets Fixtures
Faucets Fixtures 1
HOT AND COLD REVERSED
Hot and cold controls appeared to be reversed at the time of inspection. Recommend a qualified contractor to evaluate and repair or replace supply lines as needed.
6.9.2 – Faucets Fixtures
Faucets Fixtures 2
SPRAYER NOT WORKING
The faucet sprayer did not work at the time of inspection. Recommend a qualified contractor to evaluate and repair or replace as needed.
6.10.1 -Drain Waste and Vent System 
Drain Waste and Vent System 1
FLEX PIPE

The sink drain line had a flex pipe used as part of the drain line. Flexible drain lines can smell, clog, leak or fail. Flex lines design includes multiple folds in which moisture may become trapped and mold may grow.  A qualified contractor should evaluate and repair or replace as necessary.

6.10.2 – Drain Waste and Vent System
Drain Waste and Vent System 2
SLOPE INCORRECT
The sink drain pipe appeared to slope in the wrong direction. The drain line should have a slight slope away from the fixture to allow for proper draining and to prevent water and debris from resting inside the pipe.  A qualified contractor should evaluate and repair or replace as necessary.
6.13.1 – Dishwasher
Dishwasher 1
DIRTY – DRAIN LINE
The dishwasher drain line was dirty and/or possibly clogged at the time of inspection. This may be related to the lack of a “high loop” in the drain line. A high loop in the drain hose is to keep water from settling in the hose to prevent any odors from backing up into the dishwasher. A smell or mold may appear if not corrected. Recommend a qualified contractor to evaluate and repair or replace as needed.
6.15.1 – Range Hood
Range Hood1
THE LIGHT DID NOT WORK
The vent hood light was not working at the time of inspection.  A qualified contractor should evaluate and repair or replace as necessary.
6.17.1 – Refrigerator
Refrigerator 1
WATER/ICE DISPENSER NOT OPERATIONAL

Although outside the scope of a general home inspection, the inspector noted the refrigerator ice and/or water dispenser was not working.  A qualified contractor should evaluate and repair or replace as necessary.

 7 – Laundry
7.7.1 – Windows
Windows 1
WORN OR NEARING THE END OF LIFE EXPECTANCY
Windows installed in the home appeared to be worn or aged. This apparent condition can mean the windows are deteriorated or difficult to operate, and can also mean they are not consistent with current efficiency standards. They were possibly original and were either at or near their serviceable lifespan. Recommend further evaluation by a qualified contractor and budgeting for potential future replacement.
7.8.1 – Floors
Floors 1
CRACKED/DAMAGED TILE
The tile floor was cracked/damaged.  A qualified contractor should evaluate and repair or replace as necessary.
7.9.1 – Electrical Outlets
Floors 1
GFCI PROTECTION IS NOT PRESENT

An outlet did not provide Ground Fault Circuit Interrupter (GFCI) protection. Although GFCI protection of circuits may not have been required at the time in which this home was built, safe building practices have improved with the passage of time and building standards have changed to reflect current understanding. The inspector recommends updating the existing electrical circuits to include GFCI protection. A qualified contractor should evaluate and repair or replace as necessary.

7.13.1 – Washer Drain
Washer Drain 1
MISSING P-TRAP
The drain line did not have a p-trap installed at the time of inspection. A p-trap is necessary in order to prevent sewer gases from entering the home. Recommend a qualified contractor to evaluate and repair or replace as needed.
 9 – Bathroom
9.3.1 – Exhaust Fan
Exhaust Fan 1
DAMAGED/MISSING COVER
The bathroom exhaust fan had a damaged or missing cover.  A qualified contractor should evaluate and repair or replace as necessary.
9.3.2 – Exhaust Fan
Exhaust Fan 2
DIRTY
The bathroom exhaust fan was very dirty and possibly clogged.  A qualified contractor should evaluate and repair or replace as necessary.
9.5.1 – Floors
Floors 1
Floors 2
CRACKED/DAMAGED TILE
The tile floor was cracked/damaged.  A qualified contractor should evaluate and repair or replace as necessary.
9.5.2 – Floors
Floors 3
SLOPED
The floor has a dip or is sloped in areas.

Recommend a qualified contractor to evaluate and repair or replace as needed.

9.10.1 – Drain Waste and Vent System
Drain Waste and Vent System 1
CLOGGED/SLOW – SINK DRAIN
The sink drain line was clogged or drains slowly. A qualified contractor should evaluate and repair or replace as necessary.
9.12.1 – Plumbing Fixtures
Plumbing Fixtures 1
LOOSE IN WALL – SHOWER ARM

A shower supply arm was loose in the wall.  This will cause caulking/sealant to deteriorate at an accelerated rate and may allow water to enter the wall. Over time, this could potentially put added stress on the plumbing connections and develop a leak. Recommend a qualified contractor evaluate and repair or replace it as necessary.

9.12.2 – Plumbing Fixtures
Plumbing Fixtures 2
LEAK – SHOWER HEAD
There was a leak at the shower head connection at the time of inspection. Recommend a qualified contractor to evaluate and repair or replace as necessary.
9.13.1 – Toilets
Toilets 1
FLUSH-HOLD LEVER DOWN
The toilet won’t flush unless the lever is held down briefly.  A qualified contractor should evaluate and repair or replace as necessary.
9.13.2 – Toilets
Toilets 2
LOOSE ON THE FLOOR
The toilet was loose on the floor. This condition typically is caused by loose bolts or nuts and/or missing floor seals. The loose toilet can result in leaks, water damage, and mold, as well as damage to the toilet, water supply lines, bolts, and drainage pipes. A qualified contractor should evaluate and repair or replace as necessary.
9.14.1 – Tub, Shower Area
Tub, Shower Area 1
MISSING/DAMAGED GROUT
Tiles on the wall in the bath/shower area had missing or damaged grout.  A qualified contractor should evaluate and repair or replace as necessary.
 
10 – Plumbing
10.1.1 – Main Water Shut-Off Valve
Main Water Shut-Off Valve 1
CORRODED – VALVE
The main water shutoff valve was corroded.

The valve is not and was not operated during the scope of a home inspection.

Recommend a qualified contractor should evaluate and repair or replace as necessary.

10.4.1 – Water Pressure
Water Pressure 1
HIGH WATER PRESSURE
The property water supply pressure is measured at the exterior faucet or laundry appliance hose bib. Property water supply pressure exceeded the 80 pounds per square inch (PSI) limit considered the maximum allowable by generally accepted current standards. Excessively high water pressure can stress connections in the plumbing system and appliances is likely to cause leaks.

A qualified contractor should install a pressure regulator or evaluate and repair or replace one as necessary.

 12 – Heating
12.3.1 – Combustion Air Supply
NOT PRESENT

The combustion air supply for this appliance was not present. A qualified contractor should evaluate and make necessary corrections according to current standards.

The fresh air supply is recommended by manufacturers for the efficient operation of fuel-burning appliances. Years ago, the air could come from inside or outside the building, however, more recent standards prefer for combustion air to come from the outside only.

12.9.1 – Air Filter
Air Filter 1
NOT SECURED
The HVAC system air filter was not properly secured. This condition reflects a lack of regular maintenance of the HVAC system. Clogged filters can restrict airflow and increase internal temperatures. A clean air filter will help increase the efficiency and prolong the life expectancy of the heating and cooling system. Due to the damage that can be caused by dirty or clogged coils, recommend replacing the filter, as well as cleaning, servicing, and evaluating the HVAC system by a qualified HVAC professional and repair or replace as necessary.
12.10.1 – Blower
Blower 1
BLOWER, CABINET DIRTY

The blower motor, wheel, and/or cabinet appeared to be dirty at the time of inspection. Blower fans/wheels are subjected to constant dirt, dust, and lint and can become overly dirty when not cleaned on a regular basis and even faster if the air filters are not changed regularly.

A qualified contractor should evaluate, clean, and service as necessary, and certify the unit is in good working order.

 13 – Cooling
13.1.1 – Cooling System Information
Cooling System Information 1
BEYOND TYPICAL LIFE EXPECTANCY
Due to the year of manufacture, the cooling system is assumed to be near the end of its expected service life. Regular maintenance and monitoring of its condition are recommended. Budgeting for repairs and future replacement is recommended. A qualified contractor should evaluate to clean, service/repair/replace as necessary, and certify the unit if possible.  InterNACHI’s Standard Estimated Life Expectancy Chart for Homes
13.2.1 – AC Refrigerant Lines
AC Refrigerant Lines 1
DAMAGED INSULATION
The air-conditioner refrigerant suction line (large, insulated) has damaged or missing insulation in areas. A qualified contractor should evaluate and repair/replace as necessary.
13.3.1 – AC Compressor
AC Refrigerant Lines 1
CLEAN/SERVICE
Due to the current conditions at the time of inspection, the air conditioner is recommended to be cleaned, evaluated, and serviced by a qualified contractor. Consult with your real estate agent for your available options prior to closing.
 
14 – Structural Basement
14.2.1 – Basement Floor
Basement Floor 1
CRACKED – COMMON

The concrete floor in the basement was cracked in areas. These cracks appear to be common cracks indicating regular settlement or heaving, but not necessarily structural problems. Recommend a qualified contractor to evaluate to make further recommendations and repair as necessary.

Axium recommends our premier partner – Level Engineering. They can be contacted at 720-706-8540 or online at www.axiuminspections.com/structural-engineer.

14.3.1 – Foundation Wall
Foundation Wall 1
MINOR CRACKS

There were minor to moderate cracks in the basement foundation wall. These cracks should be sealed to prevent moisture intrusion and monitored for further movement. Further analysis by a licensed structural engineer is recommended. Axium recommends our premier partner – Level Engineering. They can be contacted at 720-706-8540 or online at www.axiuminspections.com/structural-engineer.

14.3.2 – Foundation Wall
Foundation Wall 2
SIGNS OF REPAIR

The foundation wall has signs of repairs. Recommend asking the current homeowner for more information. Recommend further evaluation from a qualified contractor should the repairs be excessive or of visibly poor quality.

14.3.3 – Foundation Wall
Foundation Wall 3
DAMAGE TO CONCRETE
The visible concrete foundation wall surface was damaged or deteriorated in areas. Recommend a qualified contractor to evaluate and repair or replace as needed.
14.5.1 – Moisture Intrusion
Moisture Intrusion 1
EFFLORESCENCE
Efflorescence (white powdery substance) on the wall indicates moisture is in contact with the concrete or masonry. This does not necessarily indicate that intrusion will occur. I recommend checking the gutters and the downspout drain lines for proper operation. Also, waterproofing paint could be applied to the interior side of the wall if necessary. Efflorescence is found on many properties without water intrusion occurring inside the property. But, it should alert you to the possibility that future steps may be needed. A qualified contractor should evaluate and repair as necessary.
14.5.2 – Moisture Intrusion
Moisture Intrusion
MOISTURE INTRUSION

The visible areas of the basement showed signs of possible previous moisture intrusion and/or deterioration. A qualified contractor should evaluate and repair or replace as necessary.

14.6.1 – Floor Structure & Supports
Floor Structure & Supports
Floor Structure & Supports 2
Floor Structure & Supports 3
SUPPORTS NOT INSTALLED CURRENT STANDARDS

The structural supports did not appear to be installed in accordance with current construction standards. Further analysis by a licensed structural engineer is recommended. Axium recommends our premier partner – Level Engineering.  They can be contacted at 720-706-8540 or online at www.axiuminspections.com/structural-engineer

14.6.2 – Floor Structure & Supports
Floor Structure & Supports 4
MODIFICATIONS

Modifications and repairs or additions were present in the floor structure support system. Recommend qualified contractors evaluate and repair or replace as needed.

14.6.3 – Floor Structure & Supports
Floor Structure & Supports 5
Floor Structure & Supports 6
DAMAGED SUPPORTS
Floor supports are damaged. Recommend qualified contractor repair and replace as necessary.
14.6.4 – Floor Structure & Supports
Floor Structure & Supports 7
Floor Structure & Supports 8
DAMAGE FROM FIRE

Damaged from fire. Recommend qualified contractor repair and replace as necessary.

14.7.1 – Insulation
NO INSULATION

There is no insulation on the basement exterior walls or floor system. Heat loss can occur more on this property than one that is properly insulated. A qualified contractor should evaluate and install as necessary.

14.8.1 – Vapor Barriers
VAPOR BARRIER NOT INSTALLED

A vapor barrier was not installed in the basement at the time of the inspection. A qualified contractor should evaluate and install as necessary.

14.9.1 – Electrical in Basement
Electrical in Basement 1
DAMAGED OR EXPOSED WIRING

Damaged or exposed wiring was discovered. A qualified contractor should evaluate and repair or replace as necessary.

 15 – Structural Crawlspace
15.3.1 – Moisture Intrusion
Moisture Intrusion 1
WATER DAMAGE AROUND PLUMBING
Water damage was visible in the crawlspace floor structure around plumbing lines. There may be a past or current leak in the nearby drain or supply lines that could further stain or rot wood if not corrected.
15.8.1 – Electrical in Crawlspace
Electrical in Crawlspace 1
JUNCTION BOX MISSING COVER PLATE
The splice/Junction box was missing a cover plate. A qualified contractor should evaluate and repair or replace as necessary.
 16 – Sewer Scope
16.1.1 – System Information
COMMON LINE

This sewer system is a part of a commonly-shared sewer line with additional condo/townhome units. Conditions of the common line may not be accessible or visible for inspection, including any potential problems. Any such potential problems will require further research into the responsibility and maintenance of the shared line. We recommend investigating this prior to closing.

16.3.1 – Sewer Line Condition
*MINOR TO MODERATE BUILDUP, DEBRIS, AND/OR SLUDGE

Sludge is a sticky concoction of soap scum, grease, hair, food particles, and even dissolved minerals in the water. Once a layer of sludge forms, more sludge tends to accumulate in that segment of the pipe, increasingly narrowing the size of the pipe until only a small channel allows free flow of water.

We recommend consulting a qualified drain cleaning contractor within a year to have the line cleaned and reinspected.

16.3.2 – Sewer Line Condition
*STANDING WATER

The is one or more sections of standing water in the line. Ideally, all water should drain from the line, but areas of standing water will form when the flow is restricted or significantly slowed. This is usually caused by improper pitch, bellies, or obstructions in the line. We recommend the line be cleaned by a qualified cleaning contractor and then reinspected to determine the cause of the standing water. A licensed plumber may need to be consulted to determine any necessary corrective actions.

16.4.1 – Overall Recommendations
**FURTHER EVALUATION

The main sewer line appears to be compromised. We recommend consulting with a sewer line repair/replacement contractor for further evaluation.

16.4.2 – Overall Recommendations
*REINSPECTION

Any time service cleaning or repairs are performed on the sewer line, it is recommended to reinspect the line to ensure it was properly cleaned, repaired, or replaced. This will also ensure that the sewer line was not damaged or compromised during the cleaning, repair, or replacement.

16.4.3 – Overall Recommendations
*UNABLE TO REACH CITY TAP – INTERNAL LINE CONFIGURATION

Due to the complexity of the sewer line(s), we were not able to evaluate the entirety of the sewer main.  Systems with a large number of angled turns in the line create friction on the sewer scope cable and can be problematic in terms of evaluating the line all the way to its connection to the city main. We are not a plumbing company and cannot alter the current condition or layout of the system. We highly recommend that everything be double-checked by a licensed plumber or qualified contractor prior to your objection (or any other deadline).  Please contact our office at 303-831-1202 if you’d like us to coordinate a re-visit from a 3rd party sewer scope provider at no charge.

 19 – Water Heating Equipment
19.1.1 – General Information
General Information 1
OLDER THAN 10 YEARS

The water heater was at or beyond its warranty and/or expected life expectancy.

The water heater age was determined by the photo included in this report. According to the U.S. Department of energy, these major appliances are intended to run for between 8 and 12 years. Be advised that every water heater will age differently relative to the following life span factors: water quality, mineral buildup, frequency of flushing, the volume of water utilized, size of the tank, brand, and quality of water heater. Although it was operating at the time of the inspection, the inspector can not determine the remaining life of the water heater.

19.3.1 – Pipe Connections
Pipe Connections 1
MISSING FLEX TUBING

The piping to the water heater is missing flex tubing to prevent the piping from breaking in case the concrete floor heaves or settles.

19.6.1 – Combustion Air Supply
NOT PRESENT

The combustion air supply for this appliance was not present. A qualified contractor should evaluate and make necessary corrections according to current standards.

The fresh air supply is recommended by manufacturers for the efficient operation of fuel-burning appliances. Years ago, the air could come from inside or outside the building, however, more recent standards prefer for combustion air to come from the outside only.

19.11.1 – Burn Chamber
Burn Chamber 1
RUST CORROSION
The water heater burn chamber had rust/corrosion visible. A qualified contractor should evaluate and repair or replace as necessary.
19.12.1 – Operation & Response to Controls
Operation & Response to Controls 1
FLAMES

Flames were not entirely burning a blue color. Orange and yellow flames may be an indicator that the fuel-air mixture is not right and gas may not be burning as efficiently as possible. Recommend a qualified contractor evaluate to adjust, repair, or replace fuel-burning components as necessary.