![Flue Gas Vent Pipes 1](https://cdn.spectora.com/observation_photos/edited_images/0acf9267-186d-4bcd-b9fc-62f40b46b794/original/photo.jpg?1660321704)
One or more combustion appliance exhaust flue(s) did not extend far enough above the roof. To ensure proper and safe operation, exhaust flues should extend at least 3 feet above the roof, and 2 feet above any portion of the roof within 10 feet (measured horizontally). A qualified contractor should evaluate, then repair or replace as advised prior to the inspection objection deadline.
![Roof Drainage Systems 1](https://cdn.spectora.com/observation_photos/edited_images/f1fe84c2-f7a5-493c-bbe5-1c8c7eda7d38/original/photo.jpg?1660321710)
![Roof Drainage Systems 2](https://cdn.spectora.com/observation_photos/edited_images/b0dec69c-8104-49b5-badb-f9b2ce7e997a/original/photo.jpg?1660321719)
Gutters were full of debris or granules in areas and need to be cleaned. The debris in gutters can clog drainage, or be a sign gutters are sloped improperly – Either of which may cause problems by overflowing to introduce excessive amounts of moisture to the soil beneath the foundation. Excessive moisture in soil supporting the foundation can affect its ability to support the weight of the structure above and may cause foundation damage from soil movement.
Debris in gutters can also conceal rust, deterioration or leaks that are not visible until cleaned.
A qualified contractor should evaluate and repair or replace as necessary and according to current standards.
![Attic Access 1](https://cdn.spectora.com/observation_photos/edited_images/e4959c89-8fdc-4fdc-86bb-dd25f28f2428/original/photo.jpg?1660321867)
The attic access hatch frame was damaged. A qualified contractor should evaluate and repair or replace as necessary.
![Exhaust System Vents 1](https://cdn.spectora.com/observation_photos/edited_images/a72d4ea9-da53-44df-91a5-6860fa640a19/original/photo.jpg?1660321882)
At least one vent or exhaust duct terminated in the attic and did not vent to the exterior of property.
A qualified contractor should evaluate and repair or replace as needed.
![Wall-Covering, Flashing & Trim 1](https://cdn.spectora.com/observation_photos/edited_images/db055427-6ea3-4c74-ae6d-5bfe23b48676/original/photo.jpg?1660321735)
![Wall-Covering, Flashing & Trim 2](https://cdn.spectora.com/observation_photos/edited_images/d191978b-4b35-4de2-a013-baaa6567d8d0/original/photo.jpg?1660321789)
Peeling paint was present in areas.
Recommend a qualified contractor should evaluate and repair or replace as needed.
![Electrical Fixtures 1](https://cdn.spectora.com/observation_photos/edited_images/8f70c2c2-4e74-48b7-ad9a-2aded4c5c106/original/photo.jpg?1660321752)
The inspector observed improperly terminated and/or exposed wiring in some areas of the property. Exposed wiring can be considered a safety issue till corrected.
![Walkways 1](https://cdn.spectora.com/observation_photos/edited_images/7eab13a0-68ca-4ebd-be2d-75bd59ba65c4/original/photo.jpg?1660321745)
![Walkways 2](https://cdn.spectora.com/observation_photos/edited_images/323ac563-8f0f-4a45-bbc3-5c5b05a57752/original/photo.jpg?1660321772)
The walkway(s) showed signs of heaving and/or settling in areas. Heaving is often caused by soil that has expanded in volume due to increased moisture content, or by wet soil which has expanded as it became frozen. Settlement is when the soil below a concrete slab is loose or it can no longer support the weight causing it to sink or crack.
- This causes cracks in the concrete.
- This creates trip hazards that could result in injury.
A qualified contractor should evaluate and repair or replace as necessary and according to current standards.
![Walkways 3](https://cdn.spectora.com/observation_photos/edited_images/bedbe286-b112-4d91-b8fa-b1568d6ffd83/original/photo.jpg?1660321789)
The walkway footing was loose in areas. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.
![Vegetation, Grading & Drainage 1](https://cdn.spectora.com/observation_photos/edited_images/480c5ec2-75b5-4dc1-a7dd-64e513281622/original/photo.jpg?1660321683)
![Vegetation, Grading & Drainage 2](https://cdn.spectora.com/observation_photos/edited_images/8c813750-1be3-43bd-87f3-5aafb5e46ff5/original/photo.jpg?1660321726)
Dense vegetation was present around the house in areas. This condition limited and restricted my visual inspection. Dense vegetation and landscaping up against or near the house foundation and exterior walls may be prone to water penetration and insect infestation. Trimming, pruning and some landscaping is recommended by a qualified contractor
![Vegetation, Grading & Drainage 3](https://cdn.spectora.com/observation_photos/edited_images/45f0ab3c-7a07-4a04-ba93-036b33a31efb/original/photo.jpg?1660321683)
![Vegetation, Grading & Drainage 4](https://cdn.spectora.com/observation_photos/edited_images/103fb0a8-43c1-4f2b-bfea-be5e4101958c/original/photo.jpg?1660321719)
The tree limbs that are in contact with the roof or hanging near the roof should be trimmed. Evaluating trees lies beyond the scope of the general property inspection.
Recommend a qualified contractor evaluate and repair or replace as necessary.
![Vegetation, Grading & Drainage 5](https://cdn.spectora.com/observation_photos/edited_images/48b12720-e634-4489-83ed-1cb52d98b5b7/original/photo.jpg?1660321719)
Large trees near the house have branches which overhang the property. Falling branches due to conditions such as wood decay, high winds or heavy snow loads may cause injury, death or damage. Significant weakening of large branches by conditions such as core decay may not be visible by persons without special training. Consider having these trees evaluated by a qualified arborist. Evaluating trees lies beyond the scope of the general property inspection.
Recommend a qualified contractor evaluate and repair or replace as necessary.
![Exterior Foundation Wall 1](https://cdn.spectora.com/observation_photos/edited_images/2bb60b29-4671-42f2-bc45-c356bc798f85/original/photo.jpg?1660321772)
The foundation had vertical cracks in areas. A qualified contractor should evaluate and repair as necessary before your inspection objection deadline.
![Exterior Vents 1](https://cdn.spectora.com/observation_photos/edited_images/296301cc-7871-4996-833f-83e2731ad498/original/photo.jpg?1660321752)
The vent was missing a proper cover and flap assembly. A damaged vent assembly can allow entry of water, air, or rodents into vent ducts or home. Recommend a qualified contractor to evaluate and repair or replace as necessary.
![Roof Drainage - Downspouts & Extensions 1](https://cdn.spectora.com/observation_photos/edited_images/60845e8e-c3d2-4d01-b732-b08a0f5802ea/original/photo.jpg?1660321745)
![Roof Drainage - Downspouts & Extensions 2](https://cdn.spectora.com/observation_photos/edited_images/f89f41a1-12d6-4366-bca0-ad376c261732/original/photo.jpg?1660321785)
Downspout(s) are missing the proper 6 ft. extensions. This condition may cause problems by introducing excessive amounts of moisture to the soil beneath the foundation. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.
![Additional Structures 1](https://cdn.spectora.com/observation_photos/edited_images/6dedea5f-c674-46e8-a546-b12884df5590/original/photo.jpg?1660321961)
![Additional Structures 2](https://cdn.spectora.com/observation_photos/edited_images/963dd4ec-4ae6-41ee-9544-c917435181a4/original/photo.jpg?1660321961)
Outlet and fixture covers missing showing exposed wiring. Recommend a qualified contractor for reevaluation of repair as necessary.
![Additional Structures 3](https://cdn.spectora.com/observation_photos/edited_images/f3140e85-74f3-4da2-9bb8-da73aaba715c/original/photo.jpg?1660321972)
![Additional Structures 4](https://cdn.spectora.com/observation_photos/edited_images/96a3c3ff-18ef-4613-9188-40417a420fde/original/photo.jpg?1660321972)
The windows are nearing the end of its life. Difficult to open also broken glass. Recommend a qualified contractor for reevaluation or repair as necessary.
![Additional Structures 5](https://cdn.spectora.com/observation_photos/edited_images/a1dc273e-2dc3-41b1-a8a2-2f7b98a93144/original/photo.jpg?1660321972)
![Additional Structures 6](https://cdn.spectora.com/observation_photos/edited_images/29234779-1b6b-41f9-9623-f1052408c3a7/original/photo.jpg?1660321972)
Exterior door is showing signs of weathering and damage along with peeling paint. Recommend a qualified contractor for reevaluation or repair as necessary.
![Additional Structures 7](https://cdn.spectora.com/observation_photos/edited_images/5ff6899b-c346-4228-a139-87b0cb0390d2/original/photo.jpg?1660321972)
![Additional Structures 8](https://cdn.spectora.com/observation_photos/edited_images/6498f9d9-d1d3-47a0-b41a-b8e8d14058d8/original/photo.jpg?1660321979)
Inoperable light fixture Is not working. Recommend a qualified contractor for reevaluation repair as necessary
![Additional Structures 9](https://cdn.spectora.com/observation_photos/edited_images/564bf305-f57d-43e8-9155-07be5889574b/original/photo.jpg?1660321979)
![Additional Structures 10](https://cdn.spectora.com/observation_photos/edited_images/d3974b04-470c-4d1f-8258-3a52d5415940/original/photo.jpg?1660321979)
Damage found on the ceiling area. Recommend a qualified contractor for reevaluation repair as necessary.
![Ceilings & Walls 1](https://cdn.spectora.com/observation_photos/edited_images/a94b822e-613a-4470-9260-f172f87b4ce0/original/photo.jpg?1660321889)
Baseboard trim was damaged at areas of the interior walls at the time of inspection.
Recommend a qualified contractor evaluate and repair or replace as needed.
![Ceilings & Walls 2](https://cdn.spectora.com/observation_photos/edited_images/a2c9c9ae-240b-4729-9265-31a24508c234/original/photo.jpg?1660321837)
![Ceilings & Walls 3](https://cdn.spectora.com/observation_photos/edited_images/3f5c1fe8-21aa-4524-b385-7432da1821c3/original/photo.jpg?1660321853)
![Ceilings & Walls 4](https://cdn.spectora.com/observation_photos/edited_images/42341ed9-16d3-4c79-8a95-911a6bc71b4d/original/photo.jpg?1660321853)
The walls showed signs of minor damage and wear. A qualified contractor should evaluate and repair or replace as necessary.
![Ceilings & Walls 5](https://cdn.spectora.com/observation_photos/edited_images/009eef51-3bb9-4387-9be0-63ae675aca3b/original/photo.jpg?1660321798)
![Ceilings & Walls 6](https://cdn.spectora.com/observation_photos/edited_images/0fc919a6-d38a-4800-8904-bf92c5811a66/original/photo.jpg?1660321867)
![Ceilings & Walls 7](https://cdn.spectora.com/observation_photos/edited_images/e57d238c-6d8d-4063-b4ea-ead8c5ce771e/original/photo.jpg?1660321889)
Minor cracking was visible on the interior ceilings. A qualified contractor should evaluate and repair or replace as necessary.
![Ceilings & Walls 8](https://cdn.spectora.com/observation_photos/edited_images/156caf83-37c4-4648-a528-1c4f03edcb52/original/photo.jpg?1660321798)
![Ceilings & Walls 9](https://cdn.spectora.com/observation_photos/edited_images/8ddfb44f-9ca8-4a84-aff6-e96719361ed5/original/photo.jpg?1660321809)
![Ceilings & Walls 10](https://cdn.spectora.com/observation_photos/edited_images/07791936-79f0-4e78-972d-195ff6444dd3/original/photo.jpg?1660321809)
Minor cracking was visible on the interior walls. A qualified contractor should evaluate and repair or replace as necessary.
![Ceilings & Walls 11](https://cdn.spectora.com/observation_photos/edited_images/c1e8a70f-f9fd-476e-a3be-9677cd4aa186/original/photo.jpg?1660321798)
There were “nail pops” visible on the interior walls. A qualified contractor should evaluate and repair or replace as necessary.
![Ceilings & Walls 12](https://cdn.spectora.com/observation_photos/edited_images/8608447b-5964-4143-83d3-483ea0ad4c56/original/photo.jpg?1660321861)
The paint was peeling in areas. A qualified contractor should evaluate and repair or replace as necessary.
![Ceilings & Walls 13](https://cdn.spectora.com/observation_photos/edited_images/8009d9b5-ed58-42ae-bccf-75e88e4e4571/original/photo.jpg?1660321882)
![Ceilings & Walls 14](https://cdn.spectora.com/observation_photos/edited_images/dba22d3a-59ff-4a2b-81a2-a023b5fe47f3/original/photo.jpg?1660321882)
The wall showed evidence of wood destroying organisms or insects. A qualified contractor should evaluate and repair or replace as necessary.
![Doors 1](https://cdn.spectora.com/observation_photos/edited_images/1c1aa65a-c7bb-4858-9912-a599dbbdebce/original/photo.jpg?1660321803)
The door was missing the ball catch at the top so the door does not stay closed. A qualified contractor should evaluate and repair or replace as necessary.
![Doors 2](https://cdn.spectora.com/observation_photos/edited_images/3ace5972-b8fe-4597-9f3d-8aadc71b7710/original/photo.jpg?1660321803)
![Doors 3](https://cdn.spectora.com/observation_photos/edited_images/3443a520-0c35-46cd-97a7-8d987dfa40eb/original/photo.jpg?1660321845)
The door had a damaged or missing doorstop. A qualified contractor should evaluate and repair or replace as necessary.
![Windows 1](https://cdn.spectora.com/observation_photos/edited_images/7e8220c5-b4cb-43b2-a4dc-5b7e4e68454d/original/photo.jpg?1660321809)
![Windows 2](https://cdn.spectora.com/observation_photos/edited_images/95c7d7be-5fd6-48a6-a7c4-3547a1392a1b/original/photo.jpg?1660321809)
![Windows 3](https://cdn.spectora.com/observation_photos/edited_images/a8e62999-fcad-4924-afd2-f92326cecac1/original/photo.jpg?1660321853)
A window had a sash that was difficult to slide or operate to get opened/closed. A qualified contractor should evaluate and repair or replace as necessary.
![Windows 4](https://cdn.spectora.com/observation_photos/edited_images/6d03ff25-6d35-4139-a80c-01bc743478ef/original/photo.jpg?1660321813)
![Windows 5](https://cdn.spectora.com/observation_photos/edited_images/1bb0ab70-20d3-43d7-ad1e-4743b0569c3d/original/photo.jpg?1660321813)
A window had a damaged frame at an interior area. A qualified contractor should evaluate and repair or replace as necessary.
![Windows 6](https://cdn.spectora.com/observation_photos/edited_images/2802449a-10e9-4a3a-be2f-52498c153d9d/original/photo.jpg?1660321735)
![Windows 7](https://cdn.spectora.com/observation_photos/edited_images/57632dee-e891-43c1-99c3-411ede952290/original/photo.jpg?1660321803)
![Windows 8](https://cdn.spectora.com/observation_photos/edited_images/968a95c1-bd11-4894-9d2d-07fcb5a83a41/original/photo.jpg?1660321853)
Windows installed in the home appeared to be worn or aged. This apparent condition can mean the windows are deteriorated or difficult to operate, and can also mean they are not consistent with current efficiency standards. They were possibly original and were either at or near their serviceable lifespan. Recommend further evaluation by a qualified contractor and budgeting for potential future replacement.
![Windows 9](https://cdn.spectora.com/observation_photos/edited_images/845755d8-ee35-4e48-b5b4-9a829a224c9f/original/photo.jpg?1660321861)
![Windows 10](https://cdn.spectora.com/observation_photos/edited_images/ee1b819a-0071-4552-87b5-d49f6a934f32/original/photo.jpg?1660321861)
The window had peeling paint. A qualified contractor should evaluate and repair or replace as necessary.
This property had no grounding system installed to protect devices such as switches and electrical outlets. Although this condition may have been commonly considered safe or acceptable at the time the property was originally constructed, as general knowledge of safe building practices has improved with the passage of time, building standards have changed to reflect current understanding. A qualified contractor should evaluate and repair or replace as necessary.
![Electrical Outlets 1](https://cdn.spectora.com/observation_photos/edited_images/23078cdb-ac3a-4ccc-b61a-076546e966bb/original/photo.jpg?1660321798)
![Electrical Outlets 2](https://cdn.spectora.com/observation_photos/edited_images/e36564ae-0ab9-4c0f-a81a-e2786d66b38b/original/photo.jpg?1660321803)
The inspector observed many two-prong outlets throughout the property. These are outdated outlets that should be upgraded to three-prong outlets with proper grounds. A qualified contractor should evaluate then repair or replace as advised.
![Electrical Fixtures & Switches 1](https://cdn.spectora.com/observation_photos/edited_images/073e0039-e40c-4826-9622-43e2e8852c07/original/photo.jpg?1660321889)
The light fixture had exposed splices or electrical conductors. A qualified contractor should evaluate and repair or replace as necessary.
![Electrical Fixtures & Switches 2](https://cdn.spectora.com/observation_photos/edited_images/5fa45f1b-f2d7-48f1-8008-44442c8e5c75/original/photo.jpg?1660321735)
The light fixture did not operate when the switch was turned on. Try replacing the bulb first. A qualified contractor should evaluate and repair or replace as necessary.
![Smoke & CO Detectors 1](https://cdn.spectora.com/observation_photos/edited_images/27940a5f-1e23-4437-8387-7ef834e86690/original/photo.jpg?1660321794)
Carbon monoxide detectors were not installed within a specified distance of each room lawfully used for sleeping purposes. The inspector recommends installation of carbon monoxide detectors in appropriate locations. Colorado House bill 1091 became effective on July 1, 2009 that requires Carbon Monoxide detectors to be installed in most properties that has a fuel-burning heater or appliance, a fireplace, or an attached garage.
There are no carbon monoxide detectors on the lower or upper level.
![Smoke & CO Detectors 2](https://cdn.spectora.com/observation_photos/edited_images/69ef2239-993a-4303-a2cb-935c99023d74/original/photo.jpg?1660321794)
The smoke detector was missing. A qualified person should replace as needed. The existing smoke detectors were tested if present, but they are only noted as to presence and operation as of date of inspection. Smoke detectors may work today but not work when you need them to work. This is why it is important for you to test them on a regular basis, monthly at least. Smoke detectors are recommended by the U.S. Product Safety Commission to be installed inside each bedroom and adjoining hallway and on each living level of the property and basement level.
![Ceilings & Walls 1](https://cdn.spectora.com/observation_photos/edited_images/2246a10b-bce9-48e2-82a7-8b85191b318a/original/photo.jpg?1660321897)
![Ceilings & Walls 2](https://cdn.spectora.com/observation_photos/edited_images/32379b55-479a-412a-8cdc-3b9a4f3cdbf2/original/photo.jpg?1660321904)
Baseboard trim was damaged at areas of the interior walls at the time of inspection.
Recommend a qualified contractor evaluate and repair or replace as needed.
![Ceilings & Walls 3](https://cdn.spectora.com/observation_photos/edited_images/fc164721-2227-407c-8b68-a2db9aa60354/original/photo.jpg?1660321897)
![Ceilings & Walls 4](https://cdn.spectora.com/observation_photos/edited_images/7768a322-99ef-448b-b749-136470240a35/original/photo.jpg?1660321897)
Minor cracking was visible on the interior walls. A qualified contractor should evaluate and repair or replace as necessary.
![Ceilings & Walls 5](https://cdn.spectora.com/observation_photos/edited_images/daf27192-718a-4dd9-88f4-70a31ba4073c/original/photo.jpg?1660321897)
The walls/ceilings revealed a mismatch in paint touch up. A qualified contractor should evaluate and repair or replace as necessary.
![Electrical Outlets 1](https://cdn.spectora.com/observation_photos/edited_images/5c992cec-abe6-4996-8c60-3406e150766c/original/photo.jpg?1660321904)
A GFCI outlet was defective (did not trip when tested). A qualified contractor should evaluate and repair or replace as necessary.
![Electrical Outlets 2](https://cdn.spectora.com/observation_photos/edited_images/7acd7eef-e632-4694-ac1a-049e978c49b7/original/photo.jpg?1660321904)
Ground fault circuit interrupter (GFCI) Protection was not provided for all kitchen electrical outlets. Although GFCI protection of kitchen outlets may not have been required at the time in which this property was built, as general knowledge of say fielding practices has improved with the passage of time building standards have changed to reflect current understanding. A qualified contractor should evaluate and repair or replace as necessary.
![Electrical Outlets 3](https://cdn.spectora.com/observation_photos/edited_images/d38b7b4d-ae35-4c46-b55c-4df07c14c3ec/original/photo.jpg?1660321910)
An electrical outlet was not grounded. A qualified contractor should evaluate and repair or replace as necessary.
![Windows 1](https://cdn.spectora.com/observation_photos/edited_images/3f98a612-185d-48f8-afca-2e463dbdc348/original/photo.jpg?1660321910)
A window had a sash that was difficult to slide or operate to get opened/closed. A qualified contractor should evaluate and repair or replace as necessary.
![Windows 2](https://cdn.spectora.com/observation_photos/edited_images/9671f2ba-b89d-459b-b53b-8bcfe83d50f4/original/photo.jpg?1660321910)
Windows installed in the home appeared to be worn or aged. This apparent condition can mean the windows are deteriorated or difficult to operate, and can also mean they are not consistent with current efficiency standards. They were possibly original and were either at or near their serviceable lifespan. Recommend further evaluation by a qualified contractor and budgeting for potential future replacement.
![Food Waste Disposer 1](https://cdn.spectora.com/observation_photos/edited_images/b78c3ec6-4bd4-45b8-8735-bf0687e71203/original/photo.jpg?1660321914)
The food waste disposer had exposed or improper wiring. A qualified contractor should evaluate and repair or replace as necessary.
![Dishwasher 1](https://cdn.spectora.com/observation_photos/edited_images/533e79ab-6dd4-4b73-acb2-6b25744fd9fe/original/photo.jpg?1660321918)
![Dishwasher 2](https://cdn.spectora.com/observation_photos/edited_images/a2875aac-56af-42d5-87f9-5e84670d4df4/original/photo.jpg?1660321918)
The dishwasher kickplate was loose. A qualified contractor should evaluate and repair or replace as necessary.
![Dishwasher 3](https://cdn.spectora.com/observation_photos/edited_images/4e4b538c-2b9e-4128-8f71-6fb637e5038c/original/photo.jpg?1660321794)
The dishwasher drain line was dirty and/or possibly clogged at the time of inspection. This may be related to the lack of a “high loop” in the drain line. A high loop in the drain hose is to keep water from settling in the hose to prevent any odors from backing up into the dishwasher. A smell or mold may appear if not corrected. Recommend a qualified contractor evaluate and repair or replace as needed.
![Dishwasher 4](https://cdn.spectora.com/observation_photos/edited_images/d18461b8-568c-44a5-9faa-a21940a4e062/original/photo.jpg?1660321794)
The dishwasher drain line came out from a low location and did not discharge into a higher drain pipe. Dishwasher drain lines require a “high loop” in the line in order to drain properly. A “high loop” may have been hidden behind the appliance itself. The high loop in the drain hose is to keep water from settling in the hose to prevent any odors from backing up into the dishwasher. Food or debris may become stuck in the line and smell or mold if not corrected. Recommend a qualified contractor evaluate and repair or replace as needed.
![Range Hood 1](https://cdn.spectora.com/observation_photos/edited_images/6395bfc6-7f4d-45a3-85c9-a54790ff1e23/original/photo.jpg?1660321925)
There was not a range hood vent installed in the kitchen at the time of inspection. A kitchen exhaust fan is recommended to remove grease, smoke, and fumes that are present in the air when cooking in your oven or on your stovetop.
Recommend a qualified contractor evaluate and install kitchen exhaust as necessary.
![Exhaust Fan 1](https://cdn.spectora.com/observation_photos/edited_images/b580dacd-4ef8-4e67-b68b-8ce4b0a3fde6/original/photo.jpg?1660321831)
The bathroom exhaust fan was very dirty and possibly clogged. A qualified contractor should evaluate and repair or replace as necessary.
![Ceilings & Walls 1](https://cdn.spectora.com/observation_photos/edited_images/2f121177-fd05-459f-9549-7aedd4b3cda4/original/photo.jpg?1660321831)
The walls showed signs of minor damage and wear. A qualified contractor should evaluate and repair or replace as necessary.
![Ceilings & Walls 2](https://cdn.spectora.com/observation_photos/edited_images/a9a3bd97-78e3-46eb-94ad-7f8d310ef318/original/photo.jpg?1660321837)
Minor cracking was visible on the interior ceilings. A qualified contractor should evaluate and repair or replace as necessary.
![Floors 1](https://cdn.spectora.com/observation_photos/edited_images/1b0ef769-384a-40bb-941e-6f1c466a051f/original/photo.jpg?1660321831)
Floor has a dip or is sloped in areas.
Recommend a qualified contractor evaluate and repair or replace as needed.
![Drain Waste and Vent System 1](https://cdn.spectora.com/observation_photos/edited_images/92a51457-9890-4bee-a4f3-258cf8e05a7f/original/photo.jpg?1660321825)
Flexible drain lines can clog, leak or fail. Flex lines design includes multiple folds in which moisture may become trapped and mold may grow. A qualified contractor should evaluate and repair or replace as necessary.
![Water Supply Shutoff Valves 1](https://cdn.spectora.com/observation_photos/edited_images/0b2a7690-2fbd-4aa7-b0d1-0715be6bc310/original/photo.jpg?1660321825)
The water supply shutoff valve had a damaged or missing knob. A qualified contractor should evaluate and repair or replace as necessary.
The toilet was loose at the tank to toilet connection. A qualified contractor should evaluate and repair or replace as necessary.
![Tub, Shower Area 1](https://cdn.spectora.com/observation_photos/edited_images/d9b776fa-83d0-42bb-8548-ed095a094d73/original/photo.jpg?1660321831)
![Tub, Shower Area 2](https://cdn.spectora.com/observation_photos/edited_images/a1512d09-f66b-449e-8563-f22d3471dc7f/original/photo.jpg?1660321837)
The tub/shower area had deteriorated or missing sealant (caulking or grout) at the corners and/or floor. Sealant is needed at wall corners inside the shower, corners from tub to wall, and along the floor perimeter. A qualified contractor should evaluate and repair or replace as necessary.
![Fixture Valve Installation And Temperature 1](https://cdn.spectora.com/observation_photos/edited_images/7a6bdfd4-96cb-49e7-8c37-b700a372860b/original/photo.jpg?1660321817)
The hot water in the shower did not get over 100 degrees whereas the nearby faucets did. This may indicate that either the mixing valve (safety feature to limit potential scalding) or control cartridge needs adjustment to achieve a hot shower. There may be a more significant issue, that only further evaluation can reveal.
Hot and cold supply was installed correctly and the property’s overall hot water temperature was within an acceptable range.
Recommend a qualified contractor evaluate and repair or replace as necessary.
![Fixture Valve Installation And Temperature 2](https://cdn.spectora.com/observation_photos/edited_images/7686d0df-5117-4b6f-8955-98240e092654/original/photo.jpg?1660321821)
The water supply valves and supply lines at the shower fixture in the bathroom were installed improperly with a reversed configuration. Current standards for installation produce hot water when the valve is turned to the left and cold water when the valve is turned to the right. A qualified contractor should evaluate and repair or replace as necessary.
![Water Pressure 1](https://cdn.spectora.com/observation_photos/edited_images/75fd2b63-ad73-423b-8e78-449f1da4e3f8/original/photo.jpg?1660321726)
The property water supply pressure measured at the exterior faucet or laundry appliance hose bib. Property water supply pressure exceeded the 80 pounds per square inch (PSI) limit considered the maximum allowable by generally accepted current standards. Excessively high water pressure can stress connections in the plumbing system and appliances is likely to cause leaks.
A qualified contractor should install a pressure regulator or evaluate and repair or replace one as necessary.
![Distribution Panels 1](https://cdn.spectora.com/observation_photos/edited_images/d88a81ac-64b4-48f4-8379-b5a5451e1532/original/photo.jpg?1660321757)
The circuit labels were missing, partial, or illegible at the electrical distribution panel. The circuit labels provide information describing the locations each individual circuit breaker provides power too.
Recommend a qualified contractor verify the breakers and accuracy of any existing labeling as necessary.
![Expansion Tank / Valve 1](https://cdn.spectora.com/observation_photos/edited_images/8f8929b5-ecbf-4527-a99f-ef00eb68c71e/original/photo.jpg?1660321948)
The expansion tank was not properly secured. A qualified contractor should evaluate and repair or replace as necessary.
![Drain Valve & Drip Pan 1](https://cdn.spectora.com/observation_photos/edited_images/60bbd14f-f27e-4746-ad00-2eb8ae19014f/original/photo.jpg?1660321953)
The drip pan for the water heating equipment did not have a drain line attached. A qualified contractor should evaluate and repair or replace as necessary.
![Water Temperature 1](https://cdn.spectora.com/observation_photos/edited_images/7686098f-b769-4bb6-90f9-55abd9c39dfb/original/photo.jpg?1660321921)
The water temperature was below the suggested range of 120-130 degrees. Recommend adjusting the water heater thermostat first. If water does not reach the acceptable range then a qualified contractor should evaluate and repair or replace as necessary.
![Heating System Information 1](https://cdn.spectora.com/observation_photos/edited_images/3276744a-179b-47f5-9e35-c463b974431f/original/photo.jpg?1660321936)
Due to the year of manufacture, the heating system is assumed to be near the end of its expected service life. Regular maintenance and monitoring of its condition is recommended. Budgeting for repairs and future replacement is recommended. A qualified contractor should evaluate to clean, service/repair/replace as necessary, and certify the unit if possible.
![Condensate 1](https://cdn.spectora.com/observation_photos/edited_images/02ff313f-6198-4522-a3a2-62f8e729042c/original/photo.jpg?1660321944)
The secondary drain line was capped, missing or not routed to a drain. If the primary drain line becomes blocked, this condition could cause condensation to not drain properly and possibly damage the unit. The inspector recommends installing a secondary drain or installing an over flow protection device. A qualified contractor should evaluate then repair or replace as advised.
![Cooling System Information 1](https://cdn.spectora.com/observation_photos/edited_images/3761573c-69fa-428d-aa22-0201fec434e6/original/photo.jpg?1660321780)
Due to the year of manufacture, the cooling system is assumed to be near the end of its expected service life. Regular maintenance and monitoring of its condition is recommended. Budgeting for repairs and future replacement is recommended. A qualified contractor should evaluate to clean, service/repair/replace as necessary, and certify the unit if possible.
![AC Compressor 1](https://cdn.spectora.com/observation_photos/edited_images/9a08bcbf-22ff-4d0c-ba66-ac76912c5a1f/original/photo.jpg?1660321780)
![AC Compressor 2](https://cdn.spectora.com/observation_photos/edited_images/4ed49ef3-3661-454d-9113-3e1503dae134/original/photo.jpg?1660321780)
The exterior compressor unit was not level. Over time, this may result in noisy fan operation, damage to the fan bearings and a shortened fan lifespan, or it may result in movement of the compressor housing which can cause leaks in refrigerant lines resulting in expensive service. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.
![General Information 1](https://cdn.spectora.com/observation_photos/edited_images/f189f5e3-f8cb-419b-a929-cb542165ea69/original/photo.jpg?1660321991)
The crawlspace entrance had a damaged or missing hatch cover. A proper hatch is important to keep pests out and small children safe from accidents. Recommend a qualified contractor evaluate and repair or replace as needed.
![Soil Vapor Barrier 1](https://cdn.spectora.com/observation_photos/edited_images/5167dadb-22ee-46fb-bf6e-12f187244999/original/photo.jpg?1660321985)
No soil cover was installed at the time of the inspection. Soil covers help reduce humidity levels in crawlspaces by limiting moisture evaporation into the air from soil. Reducing humidity levels can help reduce the chances for mold growth and deterioration of structural components. A qualified contractor should evaluate and install a soil cover as necessary.
![Moisture Intrusion 1](https://cdn.spectora.com/observation_photos/edited_images/abc35b4d-f28f-4bd9-af36-6223aaa326f2/original/photo.jpg?1660321985)
Efflorescence (white powdery substance) on the wall indicates moisture is in contact with the concrete or masonry. This does not necessarily indicate that intrusion will occur. I recommend checking the gutters and the downspout drain lines for proper operation. Also, a water proofing paint could be applied to the interior side of the wall if necessary. Efflorescence is found on many properties without water intrusion occurring inside the property. But, it should alert you to the possibility that future steps may be needed. A qualified contractor should evaluate and repair as necessary.