The insulation is thinner than current thermal resistance (R-value) standards.
Recommend a qualified contractor evaluate and repair or replace as needed.
The driveway showed signs of heaving and/or settling in areas. Heaving is often caused by soil that has expanded in volume due to increased moisture content, or by wet soil which has expanded as it became frozen. Settlement is when the soil below a concrete slab is loose, or it can no longer support the weight causing it to sink or crack. This condition could potentially cause a trip hazard.
A qualified contractor should evaluate and repair or replace as necessary and according to current standards.
The driveway surface was spalling in areas. This condition will continue to degrade if not corrected. A qualified contractor should evaluate and repair or replace as necessary.
Siding showed cracking and or damage in one or more places. Recommend monitoring, and if the problem exacerbates, a qualified contractor should evaluate and repair or replace as necessary and according to current standards.
Peeling paint was present in areas.
Recommend a qualified contractor should evaluate and repair or replace as needed.
Gaps at intersections of the siding, trim, and door and window openings, as well as any other holes in the siding, should be sealed with an appropriate sealant to prevent water penetration into the wall system. A qualified contractor should evaluate and repair or replace as necessary.
Minor cracking was visible on the walkway(s) in areas. Monitoring is the minimum recommendation. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.
The walkway(s) showed signs of heaving and/or settling in areas. Heaving is often caused by soil that has expanded in volume due to increased moisture content, or by wet soil which has expanded as it became frozen. Settlement is when the soil below a concrete slab is loose or it can no longer support the weight causing it to sink or crack.
- This causes cracks in the concrete.
- This creates trip hazards that could result in injury.
A qualified contractor should evaluate and repair or replace as necessary and according to current standards.
The photo-electric reverse sensors are installed too high from the garage floor surface.
The vertical distance between the photo-eye beam and the floor should be no more than 6 inches.
The ceiling and/or walls showed various signs of minor defects at numerous locations including all or some of the following: damage, cracks, holes, previous repairs, and/or improper repairs. A representative number of pictures were taken to provide an example. Should any of these issues appear excessive we recommend a qualified contractor should evaluate and repair or replace items as necessary.
The spring rail assembly is damaged or not secured to the window sash. This may cause the sash to fail to stay open if not corrected. Recommend a qualified contractor evaluate and repair or replace as necessary.
The ceiling fan did not work. A qualified contractor should evaluate and repair or replace as necessary.
Carbon monoxide detectors were not installed within a specified distance of each room lawfully used for sleeping purposes. The inspector recommends installation of carbon monoxide detectors in appropriate locations. Colorado House bill 1091 became effective on July 1, 2009 that requires Carbon Monoxide detectors to be installed in most properties that has a fuel-burning heater or appliance, a fireplace, or an attached garage.
There are no carbon monoxide detectors on the lower or upper level.
The sink drain pipe was leaking at the time of inspection. See attached video for reference. A qualified contractor should evaluate and repair or replace as necessary.
At the end of the cycle, the dishwasher would not stay latched or closed. This could be a safety feature with the appliance. A qualified contractor should evaluate and repair or replace as necessary.
The door would not latch when closed, and may need adjustment at the strike plate to latch properly. A qualified contractor should evaluate and repair or replace as necessary.
An outlet did not provide Ground Fault Circuit Interrupter (GFCI) protection. Although GFCI protection of circuits may not have been required at the time in which this home was built, safe building practices have improved with the passage of time and building standards have changed to reflect current understanding. The inspector recommends updating the existing electrical circuits to include GFCI protection. A qualified contractor should evaluate and repair or replace as necessary.
The tub/shower drain line was clogged or drains slowly. A qualified contractor should evaluate and repair or replace as necessary.
The sink basin was leaking at the overflow at the time of inspection.  A qualified contractor should evaluate and repair or replace as necessary.
The bathtub drain stop was damaged, missing or did not operate properly. Â A qualified contractor should evaluate and repair or replace as necessary.
The shower diverter was stuck and did not release when the water was turned off. Â A qualified contractor should evaluate and repair or replace as necessary.
The sink basin was leaking at the overflow of at the time of inspection.  A qualified contractor should evaluate and repair or replace as necessary.
The property had a sump pump. The sump pump did not respond to the controls. A qualified contractor should evaluate and repair/replace as necessary.
This system protects the property from water intrusion by discharging rising groundwater or seepage from surface runoff to the exterior of the property or to a waste pipe or storm drain. Sump pumps require periodic maintenance to ensure that they work when they’re needed and should be tested on an annual basis to ensure they are in working order. The pumps can be tested by lifting the float, but to avoid potential shock/electrocution hazard testing should be performed using a tool which will not conduct electricity. Pumps have a filter that should be cleaned during routine maintenance.
Screws / fasteners were missing at the electrical panel cover. A qualified contractor should evaluate and repair or replace as necessary.
Due to the year of manufacture, the heating system is assumed to be near the end of its expected service life. Regular maintenance and monitoring of its condition is recommended. Budgeting for repairs and future replacement is recommended. A qualified contractor should evaluate to clean, service/repair/replace as necessary, and certify the unit if possible. Â InterNACHI’s Standard Estimate Life Expectancy Chart for Homes
The furnace cabinet had signs of a previous leak and minor corrosion at the time of inspection. AÂ qualified contractor should evaluate and repair or replace as necessary.
The condensation line was missing a trap. This condition allows conditioned air to escape through the condensation line. A qualified contractor should evaluate then repair or replace as advised.
The visible ductwork had minor damage or gaps at the time of inspection. A qualified contractor should evaluate and repair or replace as necessary.
The blower motor, wheel, and/or cabinet appeared to be dirty at the time of inspection. Blower fans/wheels are subjected to constant dirt, dust, and lint and can become overly dirty when not cleaned on a regular basis and even faster if the air filters are not changed regularly.
A qualified contractor should evaluate, clean, and service as necessary, and certify the unit is in good working order.
The heating system did fire and appeared to be in serviceable condition at the time of the inspection. However, the interior of the cabinet was dirty. Cleaning, servicing and/or certification of the HVAC system by a qualified contractor is recommended and repaired or replaced as necessary.
Due to the year of manufacture, the cooling system is assumed to be near the end of its expected service life. Regular maintenance and monitoring of its condition is recommended. Budgeting for repairs and future replacement is recommended. A qualified contractor should evaluate to clean, service/repair/replace as necessary, and certify the unit if possible. Â InterNACHI’s Standard Estimated Life Expectancy Chart for Homes
The air-conditioner refrigerant suction line (large, insulated) has damaged or missing insulation in areas. A qualified contractor should evaluate and repair/replace as necessary.